Passive Design

Designing the building and the spaces within it to benefit from natural light, ventilation and even temperatures.

Glazing options for temperature control

Thermal performance of windows and glazed doors is determined by the type of glass used, the framing material, and the unit’s construction.

On this page:

  • Insulating glass units (IGUs)
  • Solar control glazing
  • Framing materials
  • Specifying solar heat gain coefficient (SHGC)

All of these factors together determine the thermal – as well as optical – performance of a glazing unit. All, therefore, must be considered together, along with other elements of passive design such as window size, placement and orientation, and insulation in other parts of the building envelope.

Insulating glass units (IGUs)

Insulating glass units (IGUs) may be double- or triple-glazed, although double-glazed units are more common.

A double-glazed IGU typically consists of two sheets of glass spaced apart, typically with a hollow aluminium frame that is sealed to both panes. The space between the panes may contain dry air or be filled with argon gas.

Typical insulating glass unit construction 
Typical insulating glass unit construction

Insulating glass units (IGUs) can have a significant effect on heat loss or gain, condensation, the transfer of noise, and other visual and aesthetic properties.

 

IGUs can limit heat transfer by:

  • conduction – due to the high thermal resistance of the air or gas in the space between glazing panes
  • convection – due to the inability of the still air between the panes to move and transfer heat
  • radiation – due to two or more panes interrupting the radiation of energy and the low emissivity when using a low-emissivity (low-E) surface.

The minimum spacing between glazing panes should ideally be 12 mm, but the gap can range between 10–16 mm.

Argon gas

Heat transfer through windows can be reduced by using argon gas between the panes of double glazing.

Argon gas is a low-cost, clear, non-toxic, naturally occurring gas with a lower thermal conductance than air. Use of argon between glazing panes instead of air can reduce the amount of heat conducted across the gap and improve the R-value of the glazing by 5–20%.

Argon also substantially improves the R-value of IGUs where the gap between the panes is narrower than the recommended 10 mm minimum. Therefore, if the gap between panes must be reduced to 6–8 mm, such as when retrofitting IGUs into existing timber frame windows, argon gas-filled units should be used. 

Other benefits of insulating glass units

In addition to improving the thermal performance of windows, IGUs also provide other benefits such as reducing condensation (where there is a thermal break in the frame), reducing noise transmission, and reducing the need for drapes or curtains (although these should still be installed for use on cold nights).

Secondary glazing

A less expensive option for improving the thermal performance of existing single-glazed windows is to install secondary glazing. With this, plastic film, magnetically attached plastic sheet, plain or low-E glass is installed inside the existing glass with a still air gap between them.

Research (largely carried out at BRANZ) found that secondary glazing gave R-values from 0.36 to 0.57 m2 K/W. This means that secondary glazing can be used as a functional alternative to retrofitted insulating glass units in existing domestic single-glazed window frames. (In fact, the performance exceeded the expected performance of IGUs retrofitted into the existing framing due to the secondary glazing effectively insulating the framing.)

Solar control glazing

Solar control glazing is any glazing that is tinted, has a reflective or a low-E coated surface, or has spectrally selective characteristics. Many of these properties are frequently combined in one product to provide greater solar control.

Tinted glazing

Metal oxides are added during manufacture to produce tinted glazing panes. The solar control properties of tinted glazing operate on the principle that darker colours absorb more heat than lighter colours, so a dark tinted glazing will typically reach a higher temperature than a lightcoloured tinted glazing.

Tinted glass is therefore sometimes referred to as heat-absorbing glass.

Reflective glazing

Reflective glazing, has coatings typically added to the surface of glazing panes that have a higher reflectivity than standard glass. The reflectivity can be tuned to selectively:

  • reflect short-wave solar radiation, or
  • reflect long-wave heat radiation.

The reflective ability depends on the particular coating and on the orientation of the glazing. High-reflectivity coatings generally have low light transmission properties, but reflective glazing systems with lower reflectivity and higher light transmission properties are also available for domestic use.

Reflective coatings may be added to tinted glazing to further enhance the solar control performance of the glazing.

The reflection is typically towards the side with brighter illumination, so at night, the direction of the reflectivity can change so that the reflection is to the interior.

Low-E glazing

Low-E coatings are applied to the surface of glazing panes with specific solar control properties. A microscopically thin metallic coating is added to the glazing surface, which lets light through but reflects short-wave infrared radiation. This suppresses the radiant heat flow. Converting one pane of a clear double-glazed IGU to low-E glazing is approximately equivalent to adding a third clear pane.

Low-E coated glazing is generally clear, and different types of coatings are available for high, moderate or low solar gain.

Low-E glazing is typically only used with insulated glazing units, which provide protection to the coating from the possibility of damage. The low-E coating is either:

  • on the cavity-face of the inside pane (surface 3 in the drawing below) to retain heat in colder climates
  • on the cavity face of the outside pane (surface 2 in the drawing below) to keep heat out in warmer climates.

Spectrally selective glazing

Spectrally selective glazing maximises the amount of visible light that gets into a building, but minimises the amount of solar heat that passes through. Spectrally selective glazing, under one definition, allows 25% more light (measured as visible transmittance, Tvis) to pass through than heat (measured as the solar heat gain coefficient – SHGC). This gives a light to solar gain ratio of at least 1.25.

A glazing system that passes 80% of the visible light (a Tvis of 0.8) and 64% of the solar heat (a SHGC of 0.64) therefore has a light to solar gain ratio (LSG) of 1.25. This just meets the threshold of being a spectrally selective glazing system. A higher Tvis and a lower SHGC gives better LSG, and better performance in climates with high solar intensity.  

The spectrally selective coating is typically found on an inside face of the IGU for protection.

Framing materials

The thermal performance of any window frame will depend on its construction, but in general timber, uPVC and fibreglass frames provide better thermal insulation than ordinary aluminium frames.

Fibreglass window frames are relatively new in New Zealand. Fibreglass has a vastly better thermal efficiency than aluminium. It has the same coefficient of expansion as glass, so it does not expand and contract as much as uVPC and aluminium frames. This means less stress for junctions and joints.

Thermally broken aluminium frames have a very strong spacer with a higher level of thermal performance between the inner and outer parts of the aluminium frame.

BRANZ research has shown that if thermally-broken frames and glazing with a low-e coating are specified instead of the typical low-quality double glazing, the benefits are substantial. The insulation value is increased by 65% and heating energy costs in the house are typically reduced by between 20-24%.

The following table shows the R-values for different types of frames and different glazing systems. The higher the number, the better the insulating performance.

Comparison of typical window (frame and glass) R-values (Rwindow)

Window frame material Single glazing IGU with 4 mm glass and 8 mm air space IGU with 4 mm glass and 12 mm air space IGU with 4 mm glass, 12 mm air space and low-e pane IGU with 4 mm glass, 12 mm air space, low-e pane and argon gas fill
Aluminium R0.15 R0.25 R0.26 R0.31 R0.32
Thermally broken aluminium R0.17 R0.30 R0.31 R0.39 R0.41
Timber R0.19 R0.34 R0.36 R0.47 R0.51
uPVC R0.19 R0.34 R0.36 R0.47 R0.51

The actual Rwindow is dependent on the glazing, frame material and window size.

Source: NZS 4218:2009 Thermal insulation – Housing and small buildings (provided by Standards New Zealand under licence 001148).

Specifying solar heat gain coefficient (SHGC)

When specifying glazing units:

  • Where passive solar gain is desirable, east-, north- and perhaps west-facing windows should have windows with high SHGC.
  • Where late afternoon passive solar gain is undesirable, west-facing windows should have a low SHGC (less than 0.4).
  • Where passive solar cooling is required, low SHGC windows should be used for north- and west-facing windows.
  • For south-facing windows, the SHGC has less effect, but where passive solar gain is desirable, glazing should have a high R-value and a high SHGC.

The SHGC does not necessarily have a direct correlation to visible light transmittance. For example, some advanced tinted float glazing will allow a high transmission of visible light but also have a low SHGC.

See measuring glazing performance: key concepts for an explanation of SHGC.

 

Updated: 8 February 2018